FDTC25VF / SRC25ZMX-S

FDTC25VF
Ceiling cassette – Indoor Unit

The FDTC25VF is a ceiling cassette RAC indoor unit with a nominal cooling capacity of 2.5 kW.

fdtc_il_160514104544

Technical Specifications

General Data

Nominal cooling capacity (min-max) kW 2.55 (0.9 – 3.2)
Nominal heating capacity (min-max) kW 3.45 (0.9 – 4.7)
Exterior Dimensions (H x W x D) mm Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
Net Weight kg 18.5 (Unit: 15 Panel: 3.5)
Air Flow Cooling (Hi/Me/Lo) m3/min 9 / 8 / 6.5
Air Flow Heating (Hi/Me/Lo) m3/min 9.5 / 8.5 / 7
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 36 / 32 / 29
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 38 / 33 / 29.5

Schematics

fdtc25-60vf_isl1_160514104544

SRC25ZMX-S
Ceiling cassette – Outdoor Unit

The SRC25ZMX-S is a RAC outdoor unit with a nominal cooling capacity of 2.5 kW.

src20-35zjx-hyper_ol_140514095546
FDTC25VF / SRC25ZMX-S

Technical Specifications

General Data

Nominal cooling capacity (min-max) kW 2.55 (0.9 – 3.2)
Nominal heating capacity (min-max) kW 3.45 (0.9 – 4.7)
EER (Energy Label) 4.25
COP (Energy Label) 4.11
Exterior Dimensions (H x W x D) mm 595 x 780(+62) x 290
Net Weight kg 38
Sound Pressure Level (Cooling/Heating) dB(A) 47 / 47
Energy class (cooling/heating) A+/A
SEER “Average climate”/(Energy label) 6.02
SCOP “Average climate”/(Energy label) 3.98

Elecrical Data

Pdesignc kW 2.55
Pdesignh (@-10°C) kW 2.9
Annual electricity consumption (cooling/heating) kWh/a 149 / 1020
Power Source 1Phase, 220 – 240V, 50Hz
Inrush current (220/230/240v) A 4.1
Max. running current A 9
Power consumption (cooling/heating) kW 0.60 / 0.84

Installation

Refrigerant (GWP) R410A (1975)
Designated heating season Average
Ref. Piping Size (Liquid/Gas) Ø mm 6.35 (1/4″) / 9.52 (3/8″)
Ref. Max Piping Length m Max. 15
Vertical Height differences / Outdoor is higher/lower m Max. 10 / Max. 10