FDUM71VNXVF1

FDUM71VF1
Low Static Pressure Duct Connected – Indoor Unit

The FDUM71VF1 is a low static pressure duct connected PAC indoor unit with a nominal cooling capacity of 7.1 kW.

fdum50_il_151013104046

Technical Specifications

Download Print Friendly Data Sheet HERE…

General Data

Nominal cooling capacity (min-max) kW 7.1 (3.2 – 8.0)
Nominal heating capacity (min-max) kW 8.0 (3.6 – 9.0)
Exterior Dimensions (H x W x D) mm 280 x 950 x 635
Net Weight kg 34
Air Flow Cooling (Hi/Me/Lo) m3/min 19 / 15 / 10
Air Flow Heating (Hi/Me/Lo) m3/min 19 / 15 / 10
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 33 / 29 / 25
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 33 / 29 / 25

Schematics

fdum50vf_isl1_151013104046

FDC71VNX
Low Static Pressure Duct Connected – Outdoor Unit

The FDC71VNX is a PAC outdoor unit with a nominal cooling capacity of 7.1 kW.

src71_ol_231013154604

Technical Specifications

General Data

Nominal cooling capacity (min-max) kW 7.1 (3.2 – 8.0)
Nominal heating capacity (min-max) kW 8.0 (3.6 – 9.0)
EER (Energy Label) 3.5
COP (Energy Label) 4.02
Exterior Dimensions (H x W x D) mm 750 x 880 (+88) x 340
Net Weight kg 60
Sound Pressure Level (Cooling/Heating) dB(A) 51 / 48
Energy class (cooling/heating) A/A
SEER “Average climate”/(Energy label) 5.24
SCOP “Average climate”/(Energy label) 3.9

Elecrical Data

Pdesignc kW 7.1
Pdesignh (@-10°C) kW 7
Annual electricity consumption (cooling/heating) kWh/a 475 / 2513
Power Source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Inrush current (220/230/240v) A 5
Max. running current A 17
Power consumption (cooling/heating) kW 2.03 / 1.99

Installation

Refrigerant (GWP) R410A (1975)
Designated heating season Average
Ref. Piping Size (Liquid/Gas) Ø mm 9.52 (3/8″) / 15.88 (5/8″)
Ref. Max Piping Length m Max. 50
Vertical Height differences / Outdoor is higher/lower m Max. 30 / Max. 15

Schematics

fdc70vnx-temp_file_osl1_151013102646