FDU125VNXVF

FDU125VF
High Static Pressure Duct Connected – Indoor Unit

The FDU125VF is a high static pressure duct connected PAC indoor unit with a nominal cooling capacity of 12.5 kW.

fdu_il_151013102030

Technical Specifications

General Data

Nominal cooling capacity (min-max) kW 12.5 (5.0 – 14.0)
Nominal heating capacity (min-max) kW 14.0 (4.0 – 17.0)
Exterior Dimensions (H x W x D) mm 280 x 1370 x 740
Net Weight kg 54
Air Flow Cooling (Hi/Me/Lo) m3/min 32 / 26 / 20
Air Flow Heating (Hi/Me/Lo) m3/min 32 / 26 / 20
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 40 / 34 / 29
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 40 / 34 / 29

Schematics

fdu71vf1_isl1_151013102030

FDC125VNX
High Static Pressure Duct Connected – Outdoor Unit

 

The FDC125VNX is a PAC outdoor unit with a nominal cooling capacity of 12.5 kW.

fdc100-140vnx-vsx_ol_141013155413

Technical Specifications

General Data

Nominal cooling capacity (min-max) kW 12.5 (5.0 – 14.0)
Nominal heating capacity (min-max) kW 14.0 (4.0 – 17.0)
EER (Energy Label) 3.58
COP (Energy Label) 3.71
Exterior Dimensions (H x W x D) mm 1300 x 970 x 370
Net Weight kg 105
Sound Pressure Level (Cooling/Heating) dB(A) 48 / 50

Elecrical Data

Power Source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Inrush current (220/230/240v) A 5
Max. running current A 29
Power consumption (cooling/heating) kW 3.49 / 3.77

Installation

Ref. Piping Size (Liquid/Gas) Ø mm 9.52 (3/8″) / 15.88 (5/8″)
Ref. Max Piping Length m Max. 100
Vertical Height differences / Outdoor is higher/lower m Max. 30 / Max. 15

Schematics

fdc100-125-140vnx1-temp_file_osl1_141013155823