FDT140VSVF

FDT140VF
Ceiling Cassette – Indoor Unit

The FDT140VF is a ceiling cassette PAC indoor unit with a nominal cooling capacity of 14.0 kW.

fdt_il_141013152045
Technical Specifications

General Data

Nominal cooling capacity (min-max) kW 14.0 (5.0 – 14.5)
Nominal heating capacity (min-max) kW 16.0 (4.0 – 16.5)
Exterior Dimensions (H x W x D) mm Unit: 298 x 840 x 840; Panel: 35 x 950 x 950
Net Weight kg 32.5 (Unit: 27; Panel: 5.5)
Air Flow Cooling (Hi/Me/Lo) m3/min 30 / 27 / 23
Air Flow Heating (Hi/Me/Lo) m3/min 30 / 27 / 23
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 43 / 41 / 38
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 43 / 41 / 38
Schematics
fdt100_140_isl1_171013111133

FDC140VS
Ceiling Cassette – Outdoor Unit

The FDC140VS is a PAC outdoor unit with a nominal cooling capacity of 14.0 kW.

fdc100-140vn-vs_ol_171013110522

Technical Specifications

General Data

Nominal cooling capacity (min-max) kW 14.0 (5.0 – 14.5)
Nominal heating capacity (min-max) kW 16.0 (4.0 – 16.5)
EER (Energy Label) 2.81
COP (Energy Label) 3.5
Exterior Dimensions (H x W x D) mm 845 x 970 x 370
Net Weight kg 83
Sound Pressure Level (Cooling/Heating) dB(A) 51 / 51

Elecrical Data

Power Source 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Inrush current (220/230/240v) A 5
Max. running current A 15
Power consumption (cooling/heating) kW 4.98 / 4.57

Installation

Ref. Piping Size (Liquid/Gas) Ø mm 9.52 (3/8″) / 15.88 (5/8″)
Ref. Max Piping Length m Max. 50
Vertical Height differences / Outdoor is higher/lower m Max. 30 / Max. 15

Schematics

fdc100-125-140vn-temp_file_osl1_171013111646